ZW32-40.5/1250A type outdoor high voltage  vacuum circuit breaker is the three-phase AC 50Hz, suitable for the rated  voltage of 40.5kV outdoor High-voltage Switchgear, which comply with the  national standard GB1984 "high voltage AC Circuit breakers" and  professional standards JB3855 "3.6 ~ 40.5kV outdoor AC high voltage  Vacuum Circuit Breakers" and related IEC standards. It can be used  for the control and protection of electrical equipment for industrial and  mining enterprises, power plants and substations, and  suitable for frequent operation. The circuit breaker has the ability to  break off and fast break off multiple times.
Environmental conditions
 - Ambient temperature: -35℃~ +45℃;
 - Relative  humidity: monthly average 90%, daily average 95%;
 - Saturated vapor pressure: Daily average value is no  more than 2.2×10-3 MPa; Average monthly value is not more than 1.8×10-3  MPa; In high humidity temperature drop, may condensation;
 - Altitude: ≤2000m;
 - Earthquake intensity is not more than 8;
 - There is no fire, explosion, serious pollution,  chemical corrosion, and violent vibration;
 - Can be also customized as the exact request.
Technical Data
| 1 | Rated voltage | kV | 40.5 | |
| 2 | Rated current | A | 1250/1600/2000/2500 | |
| 3 | Rated frequency | HZ | 50/60 | |
| 4 | Rated insulation level | Lightning impulse withstand voltage | kV | 185 | 
| 1 min power-frequency withstand voltage | 80, 95/95 | |||
| 6 | Rated short-circuit breaking current | kA | 25/31.5 | |
| 7 | Rated short-circuit making current (peak value) | kA | 63/80 | |
| 8 | Rated short-time withstand current | kA | 25/31.5 | |
| 9 | Rated withstand current (peak value) | kA | 63/80 | |
| 10 | Rated operating sequence | O-0.3s-CO-180s-CO | ||
| 11 | Rated short-circuit duration | s | 4 | |
| 12 | Times of breaking with the rated short-circuit current | Times | 30 | |
| 13 | Mechanical life | 10000 | ||
| 14 | Mechanism control voltage | V | AC/DC220 | |
| 15 | 1min secondary circuit power frequency withstand voltage | kV | 2 | |
| 16 | Contact open distance | mm | 16 ±1 | |
| 17 | Contact Over-travel | mm | 4±0.5 | |
| 18 | Average opening speed | m/s | 1.4±1.8 | |
| 19 | Average closing speed | m/s | 0.4-0.8 | |
| 20 | Three phase simultaneity | ms | ≤2 | |
| 21 | Contact closing bounce time | ms | ≤5 | |
| 22 | Main circuit DC resistance per phases | μΩ | ≤80 | |
| 23 | Polar distance | mm | 460 ±2 | |
| 24 | Opening time | ms | ≤50 | |
| 25 | Closing time | ms | ≤100 | |
Outline Dimension

Outline & Mounting Dimensions

ZW outdoor vacuum circuit breaker display video   ← Click to view the video


 RELATED
                        RELATED
                    
                     RELATED
                        RELATED
                    
                     RELATED
                        RELATED
                    
                     RELATED
                        RELATED
                    
                    Oil&Gas exploited
Automotive Manufacturing
Transportation & Dlistrlbutlon
Manufacture
Industrial Construction
Green Energy
Copyright ? 2024 All Rights Reserved
Back to top 
Comment
(0)