Manager Zhou
Leave a message 
	Overview
ZW-35kV (AB-35/40.5) type pole-mounted high-voltage (permanent magnet, spring) vacuum circuit breaker adopts a specially designed permanent magnet mechanism (or spring mechanism) and a highly reliable intelligent controller. This device is mainly used in medium-voltage overhead line power grids to open and close load current, overload current, and short-circuit current, and supports 0 to 3 automatic reclosing.
◆High reliability
◆Maintenance-free during the entire life
◆High mechanical and electrical life
◆Small size, light weight, easy to install
◆Standard relay protection and fast automatic reclosing function
Conditions of use
◆Ambient air temperature: -30℃ to +60℃;
◆Altitude: not more than 2000 meters;
◆Wind speed not more than 34m/s; .
◆Vibration or ground movement from outside the switchgear and control equipment is negligible;
◆Pollution level: IV ;
◆Storage temperature : -40℃ to +85℃.
Technical Parameters
| NO. | Item | Unit | Data | 
| 01 | Rated voltage | kV | 40.5 | 
| 02 | Rated current | A | 1250/1600 | 
| 03 | Rated frequency | Hz | 50 or 60 | 
| 04 | Power frequency withstand voltage 1min (wet) (dry) | kV | 80/95 | 
| 05 | Lightning impulse withstand current (peak value) | kV | 185 | 
| 06 | Rated short-circuit breaking current | kA | 31.5 | 
| 07 | Rated short-circuit making current (peak value) | kA | 80 | 
| 08 | Rated peak withstand current | kA | 80 | 
| 09 | 4S short-time withstand current | kA | 31.5 | 
| 10 | Rated operation cycle | O-0.1s-CO-3s-CO-6sCO-60s recovery | |
| 11 | Rated short-circuit current breaking times | times | 30 | 
| 12 | Mechanical lifespan | times | 20000 | 
| 13 | Control voltage of permanent magnet mechanism | V | DC220 | 
| 14 | 1-minute power frequency withstand voltage of the secondary circuit | KV | 2 | 
| 15 | Contact opening distance | mm | 16±1 | 
| 16 | contact overtravel | mm | 4±0.5 | 
| 17 | Opening speed | m/s | 1.4-1.8 | 
| 18 | Closing speed | m/s | 0.4-0.8 | 
| 19 | contact closing bounce time | ms | ≤5 | 
| 20 | Phase center distance | mm | 460±2 | 
| 21 | asynchrony of three-phase opening and closing | ms | ≤2 | 
| 22 | Conductive circuit resistance of each phase | μΩ | <120 | 
| 23 | Closing time | ms | 25~45 | 
| 24 | Opening time | ms | 20~45 | 
| 25 | weight | Kg | 295 | 