1、 The core role of Load switches in distribution networks 1. System segmentation and fault isolation -By disconnecting the load current (≤ 630A), quickly isolate the faulty section of the line and reduce the power outage range (MTTR shortened to within 30 minutes). -Suitable for 10kV/12kV distribution network, combined with Fuses to achieve short-circuit protection (with a breaking capacity of up to 20kA). 2. Equipment protection and operational safety -Design with visible fracture surface to ensure physical isolation during maintenance (fracture distance>200mm). -Mechanical interlocking function prevents misoperation (such as FN12-12D load switch).
3. Flexible networking and automation support
-The core components of the ring main unit (such as HXGN17 type) support dual power switching.
-Integrated electric operating mechanism, compatible with distribution automation system (DA/FA function).
2、 Key selection points and technical parameters
1. Voltage level matching
-Select 12kV rated voltage (such as FKN18-12) for the 10kV system, with a 20% insulation margin reserved.
2. Current capacity and breaking capacity
-Conventional routes: 400A (residential area), 630A (industrial area).
-Frequent operation scenario: Choose permanent magnet mechanism (mechanical life>10000 times).
3. Environmental adaptability design
-Coastal areas: IP65 protection+stainless steel casing (salt spray test>1000 hours).
-High cold area: -40 ℃ low-temperature lubricating grease+silicone rubber seal.
4. Intelligent function expansion
-Built in wireless temperature measurement (accuracy ± 1 ℃) and partial discharge monitoring sensor.
-Support 4G/5G communication and connect to the distribution IoT platform.
3、 Typical application scenarios and model recommendations
1. Urban and rural ring network power supply
-Scenario requirements: Dual radiation line switching, cable branch control.
-Recommended model: FLN36-12D (three station, with grounding knife).
2. Box type substation
-Scenario requirements: Compact design, high protection level (IP67).
-Recommended model: FZN25-12 (SF6 insulation, wide temperature range -30 ℃~+40 ℃).
3. New energy access
-Scenario requirement: frequent switching (photovoltaic inverter protection).
-Recommended model: VSC12 (vacuum arc extinguishing, operating life 30000 times).
4、 Operation and maintenance optimization strategy
1. Mechanical characteristic monitoring
-Check the opening and closing time every 2000 operations (standard: opening ≤ 45ms, closing ≤ 80ms).
2. Contact wear management
-Replace the silver tungsten alloy contact when the thickness is less than 3mm (detected by a laser thickness gauge).
3. Intelligent upgrade
-Add edge computing module to realize local fault diagnosis (such as arc light protection prediction).